F906 — Emergency Power
F906 emergency power: an emergency electrical system must power entrance and exit lighting, fire safety equipment and life support if normal power is lost.
In 2025 CMS recorded 2 F906 citations at 2 nursing homes (0% of homes with any F-tag citation that year); 0% were at actual-harm level or worse. Regulation: 42 CFR §483.90(c).
Content checked against CMS Appendix PP (Rev. 232) on 2026-10-31. Citation data: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23, calculated 2026-11-01.
F906 requires an emergency electrical power system that can supply power adequate at least for lighting all entrances and exits, for equipment that maintains the fire detection, alarm, and extinguishing systems, and for life support systems, if the normal electrical supply is interrupted. When life support systems are used, the facility must provide emergency power with an emergency generator, as defined in NFPA 99, located on the premises. Appendix PP says a generator is not required if the facility does not use life support systems. Life support means electrically powered equipment whose operation is necessary to maintain a resident's life, such as ventilators, and the determination depends on the residents in the facility.
Plain-language summary for reference, based on CMS State Operations Manual Appendix PP and 42 CFR Part 483. It is not the official text and not legal advice. Check the current Appendix PP and your state agency before relying on it in a Plan of Correction. Content checked against Appendix PP on 2026-10-31.
How Often F906 Is Cited
CMS publishes every nursing home deficiency citation, so the national frequency of F906 can be counted. In 2025 the file records 2 F906 citations at 2 homes, and the table below shows 2024 and 2025 with the share cited at each severity level.
| Year | Citations | Homes cited | Share of homes* | Potential harm (D-F) | Actual harm (G-I) | Immediate jeopardy (J-L) |
|---|---|---|---|---|---|---|
| 2025 | 2 | 2 | 0% | 2 | 0 | 0 |
| 2024 | 5 | 5 | 0% | 5 | 0 | 0 |
Source: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23; calculated by PoC360 on 2026-11-01. A citation is one F906 entry at one home on one survey date. *Share of homes is the homes cited under F906 divided by the 11,969 homes (2025) or 12,147 homes (2024) with at least one F-tag citation recorded that year; the file lists only cited deficiencies. Counts are national public CMS records and are not a measure of any single facility.
F906 Regulation Text
The text below is the wording of 42 CFR §483.90(c) from the eCFR, reproduced unchanged because federal regulations are public domain. It is the standard surveyors cite against, so read it next to the plain-language summary above and confirm it on the eCFR before relying on it.
(c) Emergency power. (1) An emergency electrical power system must supply power adequate at least for lighting all entrances and exits; equipment to maintain the fire detection, alarm, and extinguishing systems; and life support systems in the event the normal electrical supply is interrupted. (2) When life support systems are used, the facility must provide emergency electrical power with an emergency generator (as defined in NFPA 99, Health Care Facilities) that is located on the premises.42 CFR §483.90(c) on the eCFR →
What Surveyors Look For Under F906
CMS Appendix PP tells surveyors what to review, observe and ask when they investigate F906. The points below summarize that guidance in plain language so you can see your facility the way a surveyor will; they are not the official checklist.
- Surveyors review State fire safety authority inspection results showing the emergency power system is tested periodically and works under the Life Safety Code.
- They check lighting placement and review monthly and annual test records showing entrance and exit lighting works.
- If the facility uses life support systems, they confirm there is a working emergency generator on site; no generator is required without life support systems.
- They check that the generator starts and picks up the load within 10 seconds of a power interruption.
- Where residents are on life support, transfer switches are not tested by cutting power unless an uninterruptible power supply is available.
- They check for a type I essential electrical system where residents are on life support, such as a ventilator.
- They check that the generator and emergency electrical system are tested and maintained to NFPA 99 and 110, with records kept.
Common Deficiency Examples
F906citations arise when a facility's practice falls short of the requirement summarized above. The examples below are illustrative patterns consistent with the regulation and CMS Appendix PP guidance, not an official CMS list of citations.
- Emergency lighting that does not cover entrances and exits as required
- Facility using life support equipment, such as ventilators, with no emergency generator on the premises
- Missing or incomplete records of generator and emergency lighting testing and maintenance
- Emergency power system that does not support fire detection, alarm, or extinguishing equipment during a power interruption
What Your Plan of Correction Needs
A Plan of Correction for F906must answer CMS's five required elements: what was done for the residents affected, how other residents at risk were identified, what systemic change prevents the problem recurring, how the facility will monitor its performance, and the date compliance is achieved.
F906 PoCs should show that emergency power is both capable and tested, with records a surveyor can review:
Frequently Asked Questions
Common questions about F906 answered from CMS Appendix PP and 42 CFR Part 483, covering what the tag requires and how to approach a Plan of Correction for it.
What is F906?+
F906 emergency power: an emergency electrical system must power entrance and exit lighting, fire safety equipment and life support if normal power is lost. It is part of CMS's State Operations Manual Appendix PP, which tells surveyors how to evaluate nursing home compliance, and it appears on a CMS-2567 statement of deficiencies as an F-tag.
Does every nursing home need an emergency generator?+
No. Appendix PP says a generator is not required if the facility does not use life support systems. If life support systems are used, 42 CFR §483.90(c)(2) requires an emergency generator located on the premises.
What counts as life support equipment?+
Appendix PP defines it as electrically powered equipment whose operation is necessary to maintain a resident life, for example ventilators and suction machines needed to keep an airway open. It says deciding what is life support is a medical determination based on the residents in the facility.
How does F906 relate to the Life Safety Code K-tags?+
Appendix PP refers surveyors to NFPA 101 and NFPA 99 and to Life Safety Code survey tags K292 and K915 for additional guidance on emergency power. Concerns about the Life Safety Code under 42 CFR §483.90(a) are handled through the K-tag survey.
How often is F906 cited?+
In 2025, CMS's public Health Deficiencies file recorded 2 F906 citations at 2 nursing homes, 0% of the 11,969 homes with at least one F-tag citation that year. In 2024 the figures were 5 citations at 5 homes (0%). The counts are national and describe public CMS records, not any single facility.
What severity is F906 usually cited at?+
Of the 2 F906 citations recorded in 2025, 2 were at the potential-harm levels (D to F), 0 at actual harm (G to I) and 0 at immediate jeopardy (J to L), so 0% were actual harm or worse. Severity depends on the facts of each citation, as set out in the CMS scope and severity grid.
Sources for F906
This summary is written from the primary sources below. Read them for the official wording, and confirm the current revision before relying on it in a Plan of Correction or a survey response.
Related tags in Physical Environment
Neighbouring tags in the Physical Environment group, listed so you can compare requirements and check which tag a citation actually falls under. Each page covers its own regulation, examples and Plan of Correction guidance.
Cited on F906? See how PoC360 drafts your Plan of Correction.
Import your CMS-2567 and PoC360 helps your team draft the four Plan of Correction fields for every cited F-tag: corrective action, systemic fix, monitoring plan, and completion date.