F912 — Bedroom Square Footage
F912 bedroom square footage: bedrooms need at least 80 square feet per resident in multiple rooms and at least 100 in single rooms. 42 CFR 483.90.
In 2025 CMS recorded 254 F912 citations at 253 nursing homes (2.1% of homes with any F-tag citation that year); 0% were at actual-harm level or worse. Regulation: 42 CFR §483.90(e)(1)(ii).
Content checked against CMS Appendix PP (Rev. 232) on 2026-10-31. Citation data: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23, calculated 2026-11-01.
F912 requires bedrooms to measure at least 80 square feet per resident in multiple resident bedrooms and at least 100 square feet in single resident rooms. Appendix PP says measurement is based on usable living space: floor measurements exclusive of toilets and bath areas, closets, lockers, wardrobes, alcoves, or vestibules, unless an alcove or vestibule reasonably provides useful living area. Movable wardrobes are excluded from usable space unless they are the resident's own choice and are in addition to the closet space. Minimal protrusions such as small baseboard heating units are ignored, and the arc of a door swinging into the room is not deducted. A variation under §483.90(e)(3) may apply.
Plain-language summary for reference, based on CMS State Operations Manual Appendix PP and 42 CFR Part 483. It is not the official text and not legal advice. Check the current Appendix PP and your state agency before relying on it in a Plan of Correction. Content checked against Appendix PP on 2026-10-31.
How Often F912 Is Cited
CMS publishes every nursing home deficiency citation, so the national frequency of F912 can be counted. In 2025 the file records 254 F912 citations at 253 homes, and the table below shows 2024 and 2025 with the share cited at each severity level.
| Year | Citations | Homes cited | Share of homes* | Potential harm (D-F) | Actual harm (G-I) | Immediate jeopardy (J-L) |
|---|---|---|---|---|---|---|
| 2025 | 254 | 253 | 2.1% | 35 | 0 | 0 |
| 2024 | 303 | 298 | 2.5% | 60 | 0 | 0 |
Source: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23; calculated by PoC360 on 2026-11-01. A citation is one F912 entry at one home on one survey date. *Share of homes is the homes cited under F912 divided by the 11,969 homes (2025) or 12,147 homes (2024) with at least one F-tag citation recorded that year; the file lists only cited deficiencies. Counts are national public CMS records and are not a measure of any single facility.
F912 Regulation Text
The text below is the wording of 42 CFR §483.90(e)(1)(ii) from the eCFR, reproduced unchanged because federal regulations are public domain. It is the standard surveyors cite against, so read it next to the plain-language summary above and confirm it on the eCFR before relying on it.
(e) Resident rooms. Resident rooms must be designed and equipped for adequate nursing care, comfort, and privacy of residents. (1) Bedrooms must— [...] (ii) Measure at least 80 square feet per resident in multiple resident bedrooms, and at least 100 square feet in single resident rooms; [...]42 CFR §483.90(e)(1)(ii) on the eCFR →
What Surveyors Look For Under F912
CMS Appendix PP tells surveyors what to review, observe and ask when they investigate F912. The points below summarize that guidance in plain language so you can see your facility the way a surveyor will; they are not the official checklist.
- Surveyors may use the facility layout for square footage, and carry a tape measure to measure any room that appears small.
- They check for at least 80 square feet per resident in multiple-resident rooms and 100 square feet in single rooms, unless a variation was approved.
- Usable living space excludes toilets and baths, closets, lockers, wardrobes, alcoves and vestibules, though alcoves or vestibules of useful height may count.
- Minor protrusions of about 6 to 8 inches are ignored; larger ones are deducted from usable space.
Common Deficiency Examples
F912citations arise when a facility's practice falls short of the requirement summarized above. The examples below are illustrative patterns consistent with the regulation and CMS Appendix PP guidance, not an official CMS list of citations.
- Multiple resident bedroom with less than 80 square feet of usable space per resident, without an approved variation
- Single resident room under 100 square feet, without an approved variation
- Room measurement that included bathroom, closet, or alcove space that should have been excluded from usable living space
- Large protrusions, such as a wide column or ductwork, that reduce usable space below the minimum
What Your Plan of Correction Needs
A Plan of Correction for F912must answer CMS's five required elements: what was done for the residents affected, how other residents at risk were identified, what systemic change prevents the problem recurring, how the facility will monitor its performance, and the date compliance is achieved.
F912 PoCs should document accurate measurements and decide whether the room can lawfully stay in use as is:
Frequently Asked Questions
Common questions about F912 answered from CMS Appendix PP and 42 CFR Part 483, covering what the tag requires and how to approach a Plan of Correction for it.
What is F912?+
F912 bedroom square footage: bedrooms need at least 80 square feet per resident in multiple rooms and at least 100 in single rooms. 42 CFR 483.90. It is part of CMS's State Operations Manual Appendix PP, which tells surveyors how to evaluate nursing home compliance, and it appears on a CMS-2567 statement of deficiencies as an F-tag.
How is room size measured?+
Appendix PP says use the usable living space: floor area excluding toilets and bath areas, closets, lockers, wardrobes, alcoves, or vestibules. If an alcove or vestibule height gives useful living area, that floor area may be included.
Do furniture and door swings reduce the room size?+
Appendix PP says the door arc is not excluded, and non-permanent items the resident chose have no effect on the calculation. Minimal protrusions are ignored, but protrusions that are not minimal are deducted from usable square footage.
Can the minimum square footage be varied?+
Yes, in individual cases. 42 CFR §483.90(e)(3) allows CMS or the survey agency to permit variations to (e)(1)(i) and (ii) when the facility shows in writing that they suit residents special needs and will not adversely affect health and safety.
How often is F912 cited?+
In 2025, CMS's public Health Deficiencies file recorded 254 F912 citations at 253 nursing homes, 2.1% of the 11,969 homes with at least one F-tag citation that year. In 2024 the figures were 303 citations at 298 homes (2.5%). The counts are national and describe public CMS records, not any single facility.
What severity is F912 usually cited at?+
Of the 254 F912 citations recorded in 2025, 35 were at the potential-harm levels (D to F), 0 at actual harm (G to I) and 0 at immediate jeopardy (J to L), so 0% were actual harm or worse. Severity depends on the facts of each citation, as set out in the CMS scope and severity grid.
Sources for F912
This summary is written from the primary sources below. Read them for the official wording, and confirm the current revision before relying on it in a Plan of Correction or a survey response.