Physical Environment42 CFR §483.90(g)

F919 — Resident Call System

F919 resident call system: residents must be able to call staff from the bedside and from toilet and bathing areas through a system reaching staff.

In 2025 CMS recorded 481 F919 citations at 462 nursing homes (3.9% of homes with any F-tag citation that year); 0.8% were at actual-harm level or worse. Regulation: 42 CFR §483.90(g).

Content checked against CMS Appendix PP (Rev. 232) on 2026-10-31. Citation data: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23, calculated 2026-11-01.

F919 requires the facility to be adequately equipped so residents can call for staff assistance through a communication system that relays the call directly to a staff member or a centralized staff work area from each resident's bedside and from toilet and bathing facilities. Appendix PP says the requirement is met only if all parts of the system work, for example the system is not turned off, the volume is not too low to hear, and the light above a room is working, and calls are being answered. For wireless systems, staff who answer calls must have working devices. The call system should be accessible to a resident lying on the floor.

Plain-language summary for reference, based on CMS State Operations Manual Appendix PP and 42 CFR Part 483. It is not the official text and not legal advice. Check the current Appendix PP and your state agency before relying on it in a Plan of Correction. Content checked against Appendix PP on 2026-10-31.

How Often F919 Is Cited

CMS publishes every nursing home deficiency citation, so the national frequency of F919 can be counted. In 2025 the file records 481 F919 citations at 462 homes, and the table below shows 2024 and 2025 with the share cited at each severity level.

YearCitationsHomes citedShare of homes*Potential harm (D-F)Actual harm (G-I)Immediate jeopardy (J-L)
20254814623.9%47513
20245375124.2%526010

Source: CMS Provider Data Catalog, Nursing Home Health Deficiencies (dataset r5ix-sfxw), survey dates through 2026-09-23; calculated by PoC360 on 2026-11-01. A citation is one F919 entry at one home on one survey date. *Share of homes is the homes cited under F919 divided by the 11,969 homes (2025) or 12,147 homes (2024) with at least one F-tag citation recorded that year; the file lists only cited deficiencies. Counts are national public CMS records and are not a measure of any single facility.

F919 Regulation Text

The text below is the wording of 42 CFR §483.90(g) from the eCFR, reproduced unchanged because federal regulations are public domain. It is the standard surveyors cite against, so read it next to the plain-language summary above and confirm it on the eCFR before relying on it.

(g) Resident call system. The facility must be adequately equipped to allow residents to call for staff assistance through a communication system which relays the call directly to a staff member or to a centralized staff work area from— (1) Each resident's bedside; and (2) Toilet and bathing facilities.
42 CFR §483.90(g) on the eCFR →

What Surveyors Look For Under F919

CMS Appendix PP tells surveyors what to review, observe and ask when they investigate F919. The points below summarize that guidance in plain language so you can see your facility the way a surveyor will; they are not the official checklist.

  • Check that the system works from the bedside, toilets and bathing areas, and that calls are received and answered by staff.
  • Confirm the system is not turned off, volume is audible, call lights work, and staff are present to respond.
  • For wireless systems, check that the staff who answer calls carry working devices and respond to them.
  • Test whether a resident lying on the floor could reach and use the call system.
  • Ask residents and representatives whether calls get answered, and if the system needed repair, how often, how long and what the facility did meanwhile.
  • Ask about the routine process for confirming the system is operational, and what happens to calls during a power loss.
  • For residents whose disabilities make the system unusable, look for alternatives or auxiliary aids matching their assessment or care plan.

Common Deficiency Examples

F919citations arise when a facility's practice falls short of the requirement summarized above. The examples below are illustrative patterns consistent with the regulation and CMS Appendix PP guidance, not an official CMS list of citations.

  • Call light at the bedside or in a bathroom or shower that does not work
  • Call system turned off or volume too low at the nurses station so calls are not heard
  • Call device out of reach, such as for a resident lying on the floor or at a toilet or shower
  • Wireless system where the staff who answer calls do not have working devices
  • Call system out of order for a period without an alternate way for residents to reach staff

What Your Plan of Correction Needs

A Plan of Correction for F919must answer CMS's five required elements: what was done for the residents affected, how other residents at risk were identified, what systemic change prevents the problem recurring, how the facility will monitor its performance, and the date compliance is achieved.

F919 PoCs should cover both the equipment and the response, and an interim plan for any outage:

Gap identifiedthe rooms, bedside or bath locations, and the failure: device, volume, signal, or access
Immediate actionrepair or replacement completed, with an interim way for affected residents to reach staff, such as hourly checks, while it was out
Systemic fixa routine call system check by room, a repair request process with response times, and a plan for staff to be alerted during power loss
Accessibilityconfirmation that residents with disabilities have an accessible alternative, and that reach is checked at bedside, toilet, and bathing areas
Monitoring planperiodic testing of call devices and observation of response, with results reported to QAPI

Frequently Asked Questions

Common questions about F919 answered from CMS Appendix PP and 42 CFR Part 483, covering what the tag requires and how to approach a Plan of Correction for it.

What is F919?+

F919 resident call system: residents must be able to call staff from the bedside and from toilet and bathing areas through a system reaching staff. It is part of CMS's State Operations Manual Appendix PP, which tells surveyors how to evaluate nursing home compliance, and it appears on a CMS-2567 statement of deficiencies as an F-tag.

What does F919 require?+

A call system that relays residents calls directly to staff or a centralized staff work area from the bedside and from toilet and bathing facilities. Appendix PP says it is met only if every part of the system works and calls are being answered.

Where do concerns about slow call response go?+

Appendix PP says issues about how fast calls are answered should be examined for sufficient staffing under 42 CFR §483.35 Nursing Services, rather than as an equipment problem. F919 itself focuses on a working and accessible system.

What does a surveyor probe for?+

Appendix PP asks whether calls are received and answered, whether the system is accessible if a resident is on the floor, whether repairs were needed recently and made timely, and what happens during a loss of power. Alternatives for residents with disabilities are also checked.

How often is F919 cited?+

In 2025, CMS's public Health Deficiencies file recorded 481 F919 citations at 462 nursing homes, 3.9% of the 11,969 homes with at least one F-tag citation that year. In 2024 the figures were 537 citations at 512 homes (4.2%). The counts are national and describe public CMS records, not any single facility.

What severity is F919 usually cited at?+

Of the 481 F919 citations recorded in 2025, 475 were at the potential-harm levels (D to F), 1 at actual harm (G to I) and 3 at immediate jeopardy (J to L), so 0.8% were actual harm or worse. Severity depends on the facts of each citation, as set out in the CMS scope and severity grid.

Sources for F919

This summary is written from the primary sources below. Read them for the official wording, and confirm the current revision before relying on it in a Plan of Correction or a survey response.